UniGear ZS3.2 Design

UniGear ZS3.2 Design

Main Characteristics :

•ABB Technology
•Easy to operate and maintain
•Increased personnel safety as all operations can be done in front of the device with the door closed
•Safety interlock to avoid maloperation and fully arc-proof
•Reliable and robust 
•Compact design for optimized use of space 
•Type tested for IEC, GB/DL standards and GOST specification
•Internal arc classifications (IAC): AFLR 31.5 kA /1s
•LSC2B-PM design, metallic segregation of all compartments
•Capacitive current breaking: 800A
•Various panels meets wide range of customer requirements
•Vacuum breaker or SF6 breaker technology available in floor-rolling design
 

Applications

•Industry
•High Voltage Substations
•Power Plants
•Services
 

Technical Data:

Description Unit Data
Rated voltage kV 36…40.5
Rated power frequency withstand voltage/1 min kV 70…95
Rated lightning impulse withstand voltage kV 170….185
Rated frequency Hz 50
Rated current of busbars A 1250,1600,2000,2500,3150
Rated current of tee-offs, circuit-breaker A 1250,1600,2000,2500,3150
Rated peak withstand current kA …62, 80
Rated short-circuit breaking current kA …25, 31.5
Rated short-time withstand current 4 s kA …31.5
Loss of service continuity category - LSC 2B
Internal ARC - IAC AFLR
IP IP IP4X/IP2X
Auxiliary voltage** V DC110,220
AC110,220